NOTE:
Some numerical values have fixed permissible limits. For example, Menu 3.1.2., L.F. CUT
OFF only allows values in the range 0 to 10%. If, for example, the operator tries to enter a
value of 15%, the converter responds as follows :

6.6

Setting the current output (Fct. 1.3. and 3.3)

The current output can be programmed to the following measurement values :

Mass

Flow

Density

Temperature

Volume Flow Rate

Flow

Direction

For the current output of the MFC 081, five ranges are available :

0 to 20 mA
4 to 20 mA
0 to 20 mA warning state: 22 mA
4 to 20 mA warning state: 2 mA
4 to 20 mA warning state; 3.5 mA

All output ranges will overrange to 20.5 mA. The 4 - 20 mA ranges will under range to 3.8 mA.

All functions except flow direction have a minimum and a maximum value. When the current
output is set to one of these quantities, then the output range (4 to 20 or 0 to 20 mA) will
correspond to the appropriate minimum and maximum (see Fig. 34).

For example, to use the current output for density with the following parameters :

MIN DENSITY = 0.5g/cm

3

MAX DENSITY = 2.0g/cm

3

RANGE 4 to 20 mA

Density

Current

0.50 g/cm

3

4 mA

(minimum)

1.25 g/cm

3

12 mA

2.00 g/cm

3

20 mA

(maximum)

Key

Display
line 1

line 2

15.0

PERCENT

10.0

MAX.VALUE

Press

again to correct the number:

(0)10.0

PERCENT

Re-edit the number or press

again to

accept this value.