Foundation fieldbus data – KROHNE OPTIWAVE 7300C FOUNDATION FIELDBUS User Manual

Page 4

Advertising
background image

2

FOUNDATION FIELDBUS DATA

4

OPTIWAVE 7300 C

www.krohne.com

02/2010 - 4000621601 - AD FF OPTIWAVE 7300 R01 en

INFORMATION!

The data that follows is applicable only for fieldbus communication networks. For general
data, refer to the handbook.

Additional information (certificates, special tools, software, files...) and complete product
documentation is on the CD delivered with the device or can be downloaded free of charge
from the website (Downloadcenter).

Description

Type

FMCW radar level transmitter

Output signal

Digital signal that agrees with the FF communication protocol

Test status

Registered

Data blocks

Registered features

Alarms, events, function blocks, linking and trending

Registered function blocks

1 x Resource Block (RB)

4 x Analog Input Blocks (RB)

Other blocks

1 x Transducer Block (TB)

Communication Standard

Foundation Fieldbus protocol that agrees with IEC 61158-2

ITK version

5.1

Physical layer

Protocol

Foundation Fieldbus protocol that agrees with IEC 61158-2, galvanically isolated

Physical layer types

Standard power signaling, bus powered, non I.S.

Other features

Bus interface with integrated reverse polarity protection

Electrical connections

Device power supply (24 V input)

18...30 VDC

Current consumption on

FOUNDATION Fieldbus network

20 mA

Input and output

Output data

Level, distance, level conversion, level mass, reflection, ullage conversion or

distance mass

Input data

None

Error current FDE

Typically 0 mA (FDE =Fault Disconnection Electronic)

Link Master function

Not supported