ELECTRICAL CONNECTIONS

6

OPTIWAVE 7300 C

www.krohne.com

02/2010 - 4000621601 - AD FF OPTIWAVE 7300 R01 en

3.2 Electrical connection: PACTware™

PACTware™ is an Open Source, open configuration software for all field devices. Use
PACTware™ to configure your device. For more data, refer to "Start-up" in the handbook.

Attach a HART

®

converter to the terminals shown in the illustration that follows. We recommend

the VIATOR converter that is available as an accessory for this device. Refer to the Handbook for
more data on accessories.

CAUTION!
Before you use PACTware

to configure the device, disconnect the device from the

FOUNDATION Fieldbus segment.

CAUTION!
The HART address of the device must be set to "1". If the device is not set to "1", the device will
not operate in FOUNDATION Fieldbus networks. Refer to the Handbook for more data on how to
change the HART address.

Figure 3-2: Electrical connection: PACTware™

1 PACTware™ terminals