Wiring

T82

14

5.2

Connecting the sensor cables

Terminal assignment of the sensor terminals (® е 5, д 13).

NOTICE

When connecting 2 sensors, ensure that there is no galvanic connection between the

sensors (e.g. caused by sensor elements that are not isolated from the thermowell). The

resulting equalizing currents distort the measurement considerably.

►

The sensors must remain galvanically isolated from one another by connecting each sensor
separately to a transmitter. The transmitter provides sufficient galvanic isolation (> 2 kV AC)
between the input and output.

The following connection combinations are possible when both sensor inputs are assigned:

Sensor input 1

Sensor input 2

RTD or

resistance

transmitter,

two-wire

RTD or

resistance

transmitter,

three-wire

RTD or

resistance

transmitter,

four-wire

Thermocouple

(TC), voltage

transmitter

RTD or resistance
transmitter, two-wire

4

4

-

4

RTD or resistance
transmitter, three-wire

4

4

-

4

RTD or resistance
transmitter, four-wire

-

-

-

-

Thermocouple (TC),
voltage transmitter

4

4

4

4

5.3

Connecting the power supply and signal cables

!

CAUTION

►

Switch off power supply before installing or connecting the head transmitter. Failure to
observe this may result in destruction of parts of the electronics.

Cable specification
• A normal device cable suffices if only the analog signal is used.
• A shielded cable is recommended for HART

®

communication. Take the plant grounding

concept into consideration.

Please also observe the general procedure on (® д 13).