Operating menu and parameter description

59

Additional information

The threshold value is relevant if the sensor switching function is assigned to a HART

®

variable

(PV, SV, TV, QV).

Options:

Depends on the sensor types selected.

Factory settings

0.0 °C

"Current output" submenu
Adjustment of the analog output (4 and 20 mA current trimming)
Current trimming is used to compensate the analog output (D/A conversion). Here, the output
current of the transmitter can be adapted so that it suits the value expected at the higher-order
system.

NOTICE

Current trimming does not affect the digital HART

®

value. This can cause the measured

value shown on the plug-in display to differ from the value displayed in the higher-

order system.

The digital measured values can be adapted with the sensor trimming parameter in the menu
Expert ® Sensor ® Sensor trimming.

Procedure

1. Start

ß

2. Install an accurate amperemeter (more accurate than the transmitter) in the current loop.

ß

3. Switch on current output simulation and set the simulation value to 4 mA.

ß

4. Measure the loop current with the amperemeter and make a note of the value.

ß

5. Set the simulation value to 20 mA.

ß

6. Measure the loop current with the amperemeter and make a note of the value.

ß

7. Enter the current values determined as adjustment values in the Current trimming 4 mA / 20 mA parameters.

ß

8. End

Output current

Navigation

Setup ® Advanced setup ® Current output® Output current
Expert ® Output ® Output current

Description

Use this function to view the calculated output current in mA.