GENERAL INFORMATION

The FT400-Series flow computers are microcontroller-based

indicator/transmitters that display flow rate and total and

provide output signals. The FT415 is battery-powered and

provides a scalable pulse output. The FT420 is powered by

external DC voltage and has both pulse and 4-20 mA analog

outputs. When the FT420 is being used in the 4-20 mA mode,

it is a “two-wire” or “loop-powered” device, meaning that the

4-20 mA output signal doubles as its power supply.

The addition of a dual-relay output board (FT420 only) allows

for certain applications requiring contact output isolation (e.g.,

certain metering pumps and water treatment controls). Dual

solid state relays provide exactly the same pulse output as the

standard unit, and each can signal one external device. A non-

resettable total is also available. The FT420 can be ordered in

a plastic enclosure with a 115 Vac power supply for use with

mechanical meters, or with a built-in 115 Vac/12-24 Vdc dual

power supply for magmeters.

Both the FT415 and the FT420 can be factory-mounted on

the meter (-M) or remotely wall mounted with the brackets

provided (-W). The FT420 is also available as a panel mount

(-P) with an open back for easy installation in the user’s own

electrical enclosure. Most FT400’s can be converted from

wall-to-meter or meter-to-wall mount configurations after

installation if needed.

Housings for the -W and -M models are rugged cast aluminum,

potted and gasketed for maximum environmental protection.

A membrane keypad allows settings to be changed without

removing the cover. (Password protection, a standard feature,

can be used to prevent settings from being changed.)

**Includes password protection for tamper prevention

when needed

Lower Housing

Setup Keys**
Cover Screws

Electronics Module

Wall-Mount Brackets

Strain Relief

Display

FEATURES

**Includes password protection for

tamper prevention when needed

SPECIFICATIONS*

Lithium "C", 3.6 Vdc, replaceable, 3-5 year life

6-digit autorange, 1/2" character height

8-digit, 5/16" character height
Scaled Pulse output (0.1 sec duration 6.1 Hz max) (or High Alarm output or Low Alarm output)
Sensor pass-through Pulse output (unscaled)

None

0.1 - 9999999.9 units/pulse

Micropower GMR Sensor (square wave)

1.0 - 150 pulses/second

.001 - 99999.999

.01 - 999999.99

-30˚ to 65˚ C (-22˚ to 148˚ F)

NEMA 4X, IP66

Power

Display

Rate

Total

Outputs Current Sinking Pulse

Analog

Pulse Output Range

Input

Input Range

K-Factor Range

Flow Alarm Output Range

Operating Temperature

Environmental

FT415

FT420

*Specifications subject to change • Please consult our website for current data (www.seametrics.com).

12-30 Vdc, 4mA (4-20 mA when loop-powered)

6-digit autorange, 1/2" character height

8-digit, 5/16" character height

4-20 mA loop; 24-30 Vdc

0.1 - 9999999.9 units/pulse

5V pulse or contact closure

1.0 - 1,500 pulses/second

.001 - 99999.999

.01 - 999999.99

-30˚ to 65˚ C (-22˚ to 148˚ F)

NEMA 4X, IP66