The complete lack of moving par ts of this inser tion flow

sensor is the source of its reliability. There is no rotor to

stop turning in dir ty water and there are no bearings to

wear out. A rapidly reversing magnetic field is produced

in the lower housing, and as the fluid moves through this

field a voltage is generated. This tiny voltage is measured

and translated into a frequency signal which is propor tional

to flow rate. This square wave signal can be sent directly

to a PLC or other control, or can be conver ted using any of

the SeaMetrics family of indicators and convertors.

A modular system of electronics can be attached directly

to the flow sensor, or remotely mounted. SeaMetrics

currently offers four systems: The FT420 provides full

indication of rate and total, plus 4-20 mA output. The

AO55 provides blind 4-20 mA output, the PD10 divides

the pulse frequency, and the FS30 can be used for a

precise setpoint flow switch.

The installation fitting of the EX sensor is standard male

NPT, and can be directly threaded into ordinar y saddles or

threaded weld fittings. The EX115 and 215 include an

isolation valve, allowing hot-tap installation, or installation

and removal under pressure. The standard isolation valve

is bronze, but a 316 stainless steel valve is available as

an option if needed.

GENERAL INFORMATION

EX100/200 SERIES PARTS DIAGRAM

Housing Screw (connect ground to one)

Shaft

Cover or Module

Cable-Seal Strain Relief

Lower Housing

Sensor

Threaded Adaptor

POWER

12 - 24 Vdc, 250 mA

FLOW RANGE

0.2 – 20 ft/sec

INSTALLATION

FITTING SIZE

EX101, 201: 1.5” MNPT
EX115, 215: 2” MNPT

TEMPERATURE

Ambient: 0 – 180 F
Fluid: 32 – 212 F

PRESSURE

200 psi

MINIMUM CONDUCTIVITY

20 microsiemens/cm

CALIBRATION ACCURACY

1% of full scale

OUTPUT

Square wave pulse,
Opto isolated,
500 Hz @ 20 ft/sec

BI-DIRECTIONAL

Direction output,
Opto isolated

EMPTY PIPE DETECTION

Software, defaults to
zero flow

SPECIFICATIONS