4 rs-485 modbus, 5 product certification, 1 atex, iecex – Spectrex 40/40M Multi IR Flame Detector User Manual

Page 18: 2 fm, csa, 3 sil-2 approved (tüv), Rs-485 modbus, Product certification

Advertising
background image

Multi IR Hydrocarbon and Hydrogen Flame Detector User Guide

6

Principles of Operation

1.4.4 RS-485 Modbus

For more advanced communications, the 40/40M detector has an RS 485
Modbus-compatible output that provides data communication from a
network (up to 247 detectors) to a host computer or universal controller for
central monitoring. This feature allows for reduced installation costs, easy
maintenance and local or remote diagnostic tools.

1.4.5 Product Certification

The 40/40M Flame Detectors have the following certifications:

ATEX, IECEx, page 6

FM, CSA, page 6

SIL-2 Approved (TÜV), page 6

EN54-10, page 7

1.4.5.1 ATEX, IECEx

The 40/40M Flame Detector is certified to:

ATEX Ex II 2 GD per SIRA 07ATEX1250 and IECEx SIR. 07.0085.

Ex de IIC T5 Ta -55°C to +75°C

Ex tD A21 IP66/X7 T95°C

Ex de IIC T4 Ta -55°C to +85°C

Ex tD A21 IP66/X7 T105°C

This product is suitable to use in hazardous zones 1 and 2 with IIC gas
group vapors present.

1.4.5.2 FM, CSA

The 40/40M Flame Detector is certified to FM and CSA Explosion Proof and
Functionality per FM3260:

Class I, Division 1, Groups B, C and D, T5 Ta = 85°C.

Dust Ignition Proof – Class II/III Division 1, Groups E, F and G.

Ingress Protection – IP67, IP66, NEMA 250 Type 6P.

For more details see FM Report Project ID3029553 and CSA Report No.

2451134..

1.4.5.3 SIL-2 Approved (TÜV)

The 40/40M Flame Detector is certified to SIL-2 requirement per IEC
61508.4, Chapter 3.5.12.

The alert condition according to SIL-2 can be implemented by:

Alert signal via 0-20mA current loop.

or

Alert signal via alarm relay and fault relay.

Advertising