Multi IR Hydrocarbon and Hydrogen Flame Detector User Guide

12

Performance Considerations

Table 5: Welding Immunity Distance

Sensitivity Setting

Detection Range

Immunity Distance

1

50 ft. (15m)

>6 ft. (2m)

2

100 ft. (30m)

>12 ft. (4m)

3

150 ft. (45m)

>17 ft. (6m)

4

215 ft. (65m)

>25 ft. (7.5m)

1.5.4 Visual Indicators

One 3-color LED indicator is located inside the detector window, as shown in
Figure 4. The detector statuses are listed in Table 6.

Table 6: LED Indications

Detector Status

LED color

LED mode

Fault, BIT Fault

Yellow

4 Hz - flashing

Normal

Green

1 Hz - flashing

Warning

Red

2 Hz - flashing

Alarm

Red

Steady

Figure 4: Indication LED