1 verifying the detector wiring, Verifying the detector wiring, Table 15: model 40/40m wiring options – Spectrex 40/40M Multi IR Flame Detector User Manual

Page 40: D table 15

Advertising
background image

Multi IR Hydrocarbon and Hydrogen Flame Detector User Guide

28

Connecting the Detector

2.7.1 Verifying the Detector Wiring

The detector has five output wiring options within the Exde integral terminal
section of the enclosure. There are 12 terminals labeled 1-12.

Table 15 describes the function of each terminal for all the wiring options.

Table 15: Model 40/40M Wiring Options

Wire
Terminal
No.

Option 1
Default

Option 2

Option 3

Option 4

Option 5

1

+24 VDC

+24 VDC

+24 VDC

+24 VDC

+24 VDC

2

0 VDC

0 VDC

0 VDC

0 VDC

0 VDC

3

Manual

BIT

Manual

BIT

Manual

BIT

Manual

BIT

Manual

BIT

4

Fault

Relay N.C.

Fault

Relay N.C.

Fault

Relay N.O.

Fault

Relay N.C.

Fault

Relay N.O.

5

6

Alarm

Relay N.O.

Alarm

Relay N.O.

Alarm

Relay N.O.

Alarm

Relay N.O.

Alarm

Relay N.O.

7

Alarm

Relay C

Alarm

Relay C

Alarm

Relay C

Alarm

Relay C

Alarm

Relay C

8

0-20mA

In

Alarm

Relay N.C.

Alarm

Relay N.C.

Auxiliary

N.O.

Auxiliary

N.O.

9

0-20mA

Out

0-20mA

Out*

0-20mA

Out*

Auxiliary

C

Auxiliary C

10

RS-485+

(1)

RS-485+

(1)

RS-485+

(1)

RS-485+

(1)

RS-485+

(1)

11

RS-485-

(1)

RS-485-

(1)

RS-485-

(1)

RS-485-

(1)

RS-485-

(1)

12

RS-485

GND

RS-485

GND

RS-485

GND

RS-485

GND

RS-485

GND

*Available with the HART protocol.

Notes:

RS-485 is used for communication network as specified in Appendix C

(Terminals 10, 11, 12) and to connect (in safe area) to PC/Laptop for
configuration/diagnostics.

Alarm relay:

N.O. energized contact in wiring options 1, 4, 5.

N.O. and N.C. energized in options 2 and 3.

0-20mA is ‘Sink’ in option 1 and ‘Source’ in option 2 and 3.

0-20mA 'Source' in options 2 and 3 available with the HART protocol.

In Wiring Option 1, link Terminals 1 and 8 to change the mA output to

‘Source’.