Testing Procedures

3.3.3 Testing with Fire Simulator Model 20/20-311

The Fire Simulator Model 20/20-311 can be used to simulate exposure of
the detector to a real fire condition. The detector is exposed to radiation at
the required detection level. As a result, the detector will generate a Fire
Alarm signal. See Long Range UV/IR Fire Simulator on page 57 for more
information.

Important: If the detector is exposed to a fire simulator, the Alarm and
Accessory Relays and 0-20mA are activated during the simulation.
Therefore, automatic extinguishing systems or any external devices, which
may be activated during this process, must be disconnected.

To perform Fire Simulator Test:

1

Power up the system and wait up to 60 seconds for the detector to turn
to a normal state. The Power LED turns on.

2

Aim the Spectrex Fire Simulator Model 20/20-311 at the target point of
the detector (Figure 14), in a way that the radiation emitted by it is
facing directly towards the detector. (See Long Range UV/IR Fire
Simulator
on page 57).

3

Press the operation button once. After few seconds, a successful test
shows the results shown in Table 17.

Table 17: Results of Successful Fire Simulator Test

Component

Action

Notes

0-20mA

Turn to 20mA

For a few seconds and then return to
4mA

Alarm Relay

Activated

for a few seconds and then returns to

Normal

Auxiliary Relay

Activated

for a few seconds and then returns to
Normal

Fault Relay

Remains active
during the test

LED

Red, steady

The detector is now ready for operation.