D.1.3, Range, D.1.4 – Spectrex 40/40U-UB - UV Flame Detector User Manual

Page 71: Charging the battery, Table 26: sensitivity ranges, D.1.3 range, D.1.4 charging the battery

Advertising
background image

TM 40/40U, Rev (7) July 2013

Long Range UV/IR Fire Simulator

59

D.1.3 Range

Table 26: Sensitivity Ranges

Detector
Model

Standard Test

Range(ft./m)

Extended Test

Range with

collimator

(ft./m)

40U

14.5/ (4.5)

29/9

40UB

14.5/ (4.5)

29/9

Notes:

The minimum distance from the detector is 20 inches (50 cm).

At extreme temperatures, there is a 15% maximum reduction in the
range.

Important: Keep the Fire Simulator in a safe place when not in use.

D.1.4 Charging the Battery

The Fire Simulator uses NiCd batteries as a rechargeable power source.
When the batteries are fully charged, the simulator operates for at least 60
times without recharging. An internal buzzer is sounded when the voltage
from the batteries is lower than the required operational level.

To charge the battery:

1

Place the Fire Simulator on a table in a safe area.

2

Turn the sealed plug (next to the operation button) counter-clockwise
with a suitable wrench.

3

Connect the battery charger.

4

Charge for a maximum of 14 hours.

5

Disconnect the charger.

6

Tighten the sealed plug clockwise.

Warning: Charge the simulator only when the battery is fully discharged.
During activation of the flame simulator, buzzer activation indicates that the
battery is discharged.

Advertising