D.1.1, Unpacking, D.1.2 – Spectrex 40/40U-UB - UV Flame Detector User Manual

Page 70: Operating instructions, Figure 16: 40/40u and ub detector target point, D.1.1 unpacking, D.1.2 operating instructions

Advertising
background image

SharpEye

TM

UV Flame Detector User Guide

58

Long Range UV/IR Fire Simulator

D.1.1 Unpacking

Verify that you have received the following contents:

Delivery form

Fire Simulator with integral batteries

Battery charger

Storage case

D.1.2 Operating Instructions

Warning: Do not open the Fire Simulator to charge the batteries or for any
other reason in a hazardous area.

Caution: The following test simulates a real fire condition and may activate
the extinguishing system or other alarms. If this is not desired,
disconnect/inhibit them before the test and reconnect after the simulation.

To simulate a fire:

1

Aim the Fire Simulator towards the detector’s Target Point

Figure 16: 40/40U and UB Detector Target Point

2

When testing keep a distance of at least 50 cm (20 inches) from the
detector.

3

Press the operation button once. Fire simulation lasts for 20 seconds.
The detector sends an alarm signal (solid red LED).

4

Wait 20 seconds before repeating the test.

5

Verify that the optical window is clean.

Target Point