Precision Air Conditioning System

The computer room air conditioning equipment shall be designed specifically for precision temperature and humidity
control applications. It shall automatically monitor and control cooling, heating, humidification, de-humidification
and filtering functions for the conditioned space. The system shall be built to the highest quality engineering and
manufacturing standards and shall be subject to a functional test prior to leaving the factory.

Construction

SN, SR Units

The cabinet shall be manufactured using an external aluminium extrusion frame with aluminium corners.
Panels shall be completely removable to gain unequalled access during installation as required. The galvanised sheet
steel panels and aluminium frame and corners shall be coated with an epoxy baked powder paint to provide a durable
finish.

Standard unit colour shall be Black Grey to RAL 7021.

Cabinets shall be lined internally with various thickness fire resistant foam (BS 476) for thermal and acoustic insulation.
The insulation density shall not be less than 75 kg/m³.

The cabinet doors shall be full height, hinged and key lock secured. The hinge arrangement shall allow flexible door
opening/removal for improved access.

A propriety rubberised door seal shall reduce sound breakout and eradicate air leakage. In-seal type foam based door
seals shall not be acceptable.

The control panel is mounted on hinges to allow easy removal of filters and access to several electrical components.

The unit design shall incorporate a series of M6 fixings to the top and bottom face to ease customer ductwork
connection and reduce installation time.

SD Units

The cabinet shall be manufactured using steel frame.
Panels shall be completely removable to gain unequalled access during installation as required. The galvanised sheet
steel panels shall be coated with an epoxy baked powder paint to provide a durable finish.

Standard unit colour shall be Black Grey to RAL 7021.

Cabinets shall be lined internally with various thickness fire resistant foam (BS 476) for thermal and acoustic insulation.
The insulation density shall not be less than 75 kg/m³.

The cabinet doors shall be full height, hinged and key lock secured. The hinge arrangement shall allow flexible door
opening/removal for improved access.

A propriety rubberised door seal shall reduce sound breakout and eradicate air leakage. In-seal type foam based door
seals shall not be acceptable.

The unit design shall incorporate a series of M6 fixings to the top and bottom face to ease customer ductwork
connection and reduce installation time.

Precision Air Conditioning

SmartCool™ 6 - 200kW

11

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014