Precision air conditioning smartcool™ 6 - 200kw, Technical data sd cl00 units, Te ch nic al sd c l0 0 – Airedale SmartCool 11-233kW User Manual

Page 145: Performance data sd cl00

Advertising
background image

Technical Data SD CL00 Units

Performance Data SD CL00

Chilled water inlet and outlet temperatures

Model

Air On

15 / 20 °C

17 / 22 °C

18 / 24°C

20 / 26 °C

Temp. (°C)

TC

SC

TC

SC

TC

SC

TC

SC

/ %RH

(kW)

(kW)

(kW)

(kW)

(kW)

(kW)

(kW)

(kW)

33 / 26

101.7

101.7

89.0

89.0

79.6

79.6

66.4

66.4

SD18D115-CL00-0

35 / 24

113.3

113.3

100.8

100.8

91.8

91.8

79.0

79.0

37 / 22

125.0

125.0

112.7

112.7

103.9

103.9

91.5

91.5

33 / 26

121.7

121.7

106.8

106.8

96.1

96.1

80.6

80.6

SD22D145-CL00-0

35 / 24

135.4

135.4

120.6

120.6

110.4

110.4

95.4

95.4

37 / 22

149.1

149.1

134.5

134.5

124.6

124.6

109.8

109.8

33 / 26

159.2

159.2

139.7

139.7

125.9

125.9

105.7

105.7

SD25D180-CL00-0

35 / 24

177.1

177.1

157.8

157.8

144.6

144.6

124.9

124.9

37 / 22

195.1

195.1

176.1

176.1

163.1

163.1

143.8

143.8

33 / 26

206.1

206.1

180.7

180.7

162.6

162.6

136.4

136.4

SD31D235-CL00-0

35 / 24

229.2

229.2

204.2

204.2

186.8

186.8

161.4

161.4

37 / 22

252.6

252.6

227.9

227.9

210.9

210.9

185.8

185.8

33 / 26

237.6

237.6

208.5

208.5

188.1

188.1

158.0

158.0

SD35D270-CL00-0

35 / 24

264.3

264.3

235.6

235.6

215.9

215.9

186.6

186.6

37 / 22

291.2

291.2

262.8

262.8

243.5

243.5

214.8

214.8

Precision Air Conditioning

SmartCool™ 6 - 200kW

145

SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.1.0_04_2014