Precision air conditioning smartcool™ 6 - 200kw, Ins ta lla tio n, Glycol specific heat capacity (c – Airedale SmartCool 11-233kW User Manual

Page 65: Kj/kg k), Density (ρ) (kg/m³), Pressure drop correction factor (p

Advertising
background image

Glycol

Specific Heat Capacity (C

p

) (kj/kg K)

Water/Glycol

Temperature °C

Ethylene Glycol (Volume) / Freezing Point °C

0% / 0°C

10% / -4°C

20% / -9°C

30% / -15°C

40% / -23°C

Cp

Cp

Cp

Cp

Cp

20

4.183

3.972

3.815

3.645

3.468

25

4.181

3.981

3.826

3.660

3.485

30

4.179

3.989

3.838

3.674

3.502

35

4.178

3.998

3.849

3.688

3.518

40

4.179

4.007

3.861

3.702

3.535

45

4.181

4.015

3.872

3.716

3.552

Density (ρ) (kg/m³)

Water/Glycol

Temperature °C

Ethylene Glycol (Volume) / Freezing Point °C

0% / 0°C

10% / -4°C

20% / -9°C

30% / -15°C

40% / -23°C

ρ

ρ

ρ

ρ

ρ

20

998

1013

1030

1045

1060

25

997

1012

1028

1043

1058

30

996

1010

1026

1041

1055

35

994

1008

1024

1039

1053

40

992

1006

1022

1036

1050

45

990

1003

1020

1035

1048

Pressure Drop Correction Factor (P

x

)

Water/Glycol

Temperature °C

Ethylene Glycol (Volume)

0%

10%

20%

30%

40%

Px

Px

Px

Px

Px

20

0.983

1.0125

1.054

1.0958

1.15

(1) All data based upon ASHRAE fundamentals 2001.