Unit operating parameters, Easicool™ ezre precision air conditioning, Ope ra tion – Airedale EasiCool 6kW 64kW User Manual

Page 14

Advertising
background image

EasiCool™ EZRE

Precision Air Conditioning

14

EasiCool EZRE Operational Manual 7610207 V1.0.0_02_2013

O

pe

ra

tion

Unit Operating Parameters

Inputs and outputs can be located by the labels to the microprocessor controller.

Analogue Inputs

X/WX Unit

CW Unit

B1

Return air humidity

B1

Return air humidity

B2

Condensing Pressure

B2

Supply Air Temperature

B3

Coil Temperature

B3

Coil Temperature

B4

Not Used

B4

Not used

B5

Return Air Temperature

B5

Return air temperature

B6

Not Used

B6

Not used

Digital Inputs

ID1

Remote on/off

ID1

Remote on/off

ID2

Airflow differential pressure switch

ID2

Airflow differential pressure switch

ID3

Critical Alarm

ID3

Critical Alarm

ID4

Overheat cut-out

ID4

Overheat cut-out

ID5

Not Used

ID5

Not used

ID6

Low pressure safety switch

ID6

Not used

ID7

Compressor 1 status alarm

ID7

Not used

ID8

Compressor 2 status alarm

ID8

Not used

Analogue Outputs

Y1

Main Fan Speed Controller

Option 2 / EC Fans

Y1

Main Fan Speed Controller

Option 2 / EC Fans

Y2

Thyristor Heating

Y2

Thyristor Heating

Y3

Main Fan Speed Controller Option 1

Y3

Main Fan Speed Controller Option 1

Y4

Condenser Fan Speed Controller

Y4

Chilled Water Valve

Digital Outputs

NO1

Compressor 1

NO1

Open CW Valve

NO2

Compressor 2

NO2

Close CW Valve

NO3

Not Used

NO3

Not Used

NO4

HGRH / Heat Stage 1 / LPHW Valve Open

NO4

Heat Stage 1 / Open LPHW Valve

NO5

Heat Stage 2 / LPHW Valve Close

NO5

Heat Stage 2 / Close LPHW Valve

NO6

Heat Stage 3

NO6

Heat Stage 3

NO7

Not Used

NO7

Not Used

NO8

Common Alarm

NO8

Common Alarm

CAUTION

Inputs or outputs not required will not be connected nor will they appear on the display keypad.

SERVICE INDICATOR
The maintenance of key components such as compressors, fans and air filters can be monitored via a service indicator

which visually demonstrates the status relative to the component service intervals.

Inputs and outputs can be located by the labels to the microprocessor controller.