Refrigeration, Refrigeration 18, Easicool™ ezre precision air conditioning – Airedale EasiCool 6kW 64kW User Manual

Page 18: Main te nanc e, Maintenance

Advertising
background image

18

EasiCool EZRE Operational Manual 7610207 V1.0.0_02_2013

M

ain

te

nanc

e

EasiCool™ EZRE

Precision Air Conditioning

Maintenance

Refrigeration

Service Tools / Test Equipment

•

Refrigerant Manifold gauges

•

Spanners

•

Voltmeter

Safety Equipment

•

Safety Glasses / Goggles

•

Gloves

•

Overalls

Procedures

HP / LP Safety Pressure Switch Settings

Check operating of HP / LP cut-out,

Settings

LP cut-out – (Manual reset)
Has a 2 minute delay on start-up (similar to a Low ambient kit) plus 60 second run delay.
Low pressure cut-out 1.5 +/- 0.2 Barg
HP switch (manual reset): High pressure switch 40.25 bar +/- 1 Barg

Compressor Oil Level (Full load)

Check the compressor oil level at full load. (record oil level)

Refrigeration

Task

Frequency

3 Mths

12 Mths

60 Mths

Compare the following and compare results with commissioning records.
Suction, Liquid and Discharge pressures.

●

Refrigeration system temperatures, Suction, Liquid and

Discharge. Record superheat and sub cooling readings.

●

Check each circuit sight glass for dryness

and bubbles for indication of leaks.

●

Head pressure control is maintained.

●

Record details on F-Gas record.

●

Check compressor oil level.

●