Precision Air Conditioning

EasiCool™EZRE

Troubleshooting

FAULT

POSSIBLE CAUSE

REMEDY / ACTION

Suction pressure too low.

Low evaporator airflow.

Depending on model:
Check fan motor speed set point or
Check fan motors, belts and drives

Flash gas (bubbles in sight

glass) at expansion valve.

Investigate for refrigerant leaks,

repair and re-charge system.

Clogged filter drier (pressure /

temperature drop across it).

Replace.

Obstruction in expansion valve.

Inspect, clean or replace.

Condenser fan not operating - power on.

Motor / fan assembly jammed.

Isolate unit and check free rotation of

motor / fan assembly. If faulty - replace.

Fault at motor terminal box

supply terminals.

Isolate and check electrical

connections are secure.

Motor internal overheat protector tripped.

Carry out continuity check at terminals

“TK” in motor terminal box. If tripped and

motor hot - check bearings. If tripped

and motor cold - replace motor.

Power supply failure.

Check power supply at circuit breaker.

Wiring to motor.

Check voltage at motor terminals.

Faulty motor windings / capacitor.

Motor humming would indicate

fault in motor or capacitor.

Minimum speed set too low.

Adjust head pressure controller to suit.

Faulty pressure sensor.

Check electrical connections are

secure at controller and pressure

sensor. Replace controller and sensor

(as they are matched sets).

Faulty Controller.

Link wires “line” and “load” to

bypass controller. If motor runs

full speed - replace unit.

Condenser fan runs too fast.

Condenser fans runs only slowly.

High ambient condition or excessive re-

circulation of air around condenser coil.

Check installation against design.

Minimum set speed setting incorrect.

Adjust as necessary.

Incorrect pressure setting.

Adjust sensor screw as necessary.

Faulty Fan Speed Controller.

Replace controller and sensor

(as they are matched sets).

Faulty pressure sensor.

Replace controller and sensor

(as they are matched sets).

Motor wired incorrectly.

Check against wiring diagram

- correct as required.

Motor / capacitor faulty.

Replace.