Easicool™ precision air conditioning, Ins ta lla tio n, Unit refrigerant charge – Airedale EasiCool 6kW 64kW User Manual

Page 44: Important

Advertising
background image

EasiCool™

Precision Air Conditioning

Unit Refrigerant Charge

(kg / Circuit)

44

EasiCool Technical Manual 7535776 V1.1.0_04_2013

Ins

ta

lla

tio

n

IMPORTANT

The pipe sizes/refrigerant charges quoted are for guidance only. It is the responsibility of the installing contractor/site
engineer to check the pipe sizes/refrigerant charges are correct for each system installation and application.

Split systems may require additional oil which should be added to the low side of each compressor.

Design should be in accordance with accepted refrigeration practice to ensure good oil return to the compressor(s)
under all normal operating conditions.

Indoor Unit

Standard Condenser

Larger Condenser

(IR)

kg/Circuit

HGRH

(1)

(OR)

kg/Circuit

(OR)

kg/Circuit

kg/Circuit

V8X-EZRE

1

1.1

CR16

2.7

CR22

2.2

V10X-EZRE

1

1.1

CR16

2.7

CR22

2.2

V13X-EZRE

1.5

1.7

CR22

2.2

CR30

4.3

V15X-EZRE

1.5

1.7

CR22

2.2

CR30

4.3

V17X-EZRE

1.5

1.7

CR30

4.3

CR50

4.9

V20X2-EZRE

2.2

2.5

CR30

4.3

CR50

4.9

V22X2-EZRE

2.2

2.5

CR50

4.9

CR65

9.8

V26X2-EZRE

2.2

2.5

CR50

4.9

CR65

9.8

V28X-EZRE

2.7

3

CR50

4.9

CR65

9.8

V28X2-EZRE

2.6

2.9

CR50

4.9

CR65

9.8

V31X-EZRE

2.7

3

CR50

4.9

CR65

9.8

V31X2-EZRE

2.6

2.9

CR50

4.9

CR65

9.8

V35X-EZRE

3.3

3.7

CR50

4.9

CR65

9.8

V35X2-EZRE

3.3

3.7

CR50

4.9

CR65

9.8

V40X-EZRE

3.5

4

CR65

9.8

CR80

8.4

V40X2-EZRE

3.6

4.1

CR65

9.8

CR80

8.4

V45X2-EZRE

4.2

4.7

CR80

8.4

CR105

16.7

V50X2-EZRE

4.5

5.1

CR80

8.4

CR105

16.7

V55X2-EZRE

5.2

5.8

CR80

8.4

CR105

16.7

V60X2-EZRE

5.4

5.9

CR80

8.4

CR105

16.7

Advertising