Easicool™ precision air conditioning, Technical data upflow units wx type, Operating limits – Airedale EasiCool 6kW 64kW User Manual

Page 91

Advertising
background image

EasiCool™

Precision Air Conditioning

Technical Data Upflow Units WX Type

Performance Data

91

EasiCool Technical Manual 7535776 V1.1.0_04_2013

Te

ch

nic

al

W

X - T

yp

e

380

V

6

0H

z

V

380

V

6

0H

z

Cooling Capacity (1)

Condenser Entering/Leaving Temperature - Based on 5°C ΔT

Air On

25°C/30°C

30°C/35°C

35°C/40°C

40°C/45°C

(DB°C/%RH) TC (kW) SC (kW)

THR

(kW)

TC (kW) SC (kW)

THR

(kW)

TC (kW) SC (kW)

THR

(kW)

TC (kW) SC (kW)

THR

(kW)

V40WX-EZRE-1

22/50

40.6

40.6

54.4

40.6

40.6

54.4

39.9

39.9

54.1

38.0

38.0

53.2

24/45

42.2

42.2

56.1

42.2

42.2

56.1

41.5

41.5

55.8

39.6

39.6

55.0

26/40

43.8

43.8

57.8

43.8

43.8

57.8

43.2

43.2

57.5

41.4

41.4

56.9

V40WX2-EZRE-1

22/50

42.2

42.2

56.3

42.2

42.2

56.3

41.6

41.6

56.0

39.7

39.7

55.5

24/45

43.8

43.8

57.9

43.8

43.8

57.9

43.1

43.1

57.7

41.3

41.3

57.3

26/40

45.4

45.4

59.7

45.4

45.4

59.7

44.8

44.8

59.5

43.0

43.0

59.1

V45WX2-EZRE-1

22/50

48.4

46.8

64.2

48.4

46.8

64.2

47.7

46.4

64.0

45.6

45.0

63.2

24/45

50.0

50.0

66.0

50.0

50.0

66.0

49.3

49.3

65.7

47.3

47.3

65.0

26/40

51.7

51.7

67.8

51.7

51.7

67.8

51.0

51.0

67.5

49.0

49.0

66.9

V50WX2-EZRE-1

22/50

51.7

50.8

69.5

51.7

50.8

69.5

50.8

50.2

69.1

48.3

48.3

68.2

24/45

53.6

53.6

71.6

53.6

53.6

71.6

52.7

52.7

71.2

50.2

50.2

70.2

26/40

55.5

55.5

73.6

55.5

55.5

73.6

54.6

54.6

73.2

52.1

52.1

72.2

V55WX2-EZRE-1

22/50

59.5

55.5

80.6

59.5

55.5

80.6

58.5

54.9

80.2

55.8

53.3

79.1

24/45

61.6

59.7

82.8

61.6

59.7

82.8

60.5

59.1

82.3

57.8

57.3

81.2

26/40

63.5

63.5

84.9

63.5

63.5

84.9

62.4

62.4

84.4

59.7

59.7

83.2

V60WX2-EZRE-1

22/50

67.5

62.1

91.2

67.5

62.1

91.2

66.2

61.3

90.6

63.0

59.4

89.2

24/45

69.7

66.6

93.6

69.7

66.6

93.6

68.4

65.8

93.0

65.1

63.8

91.6

26/40

71.8

71.4

95.9

71.8

71.4

95.9

70.5

70.5

95.3

67.2

67.2

93.9

TC = Total Cooling
SC = Sensible Cooling
THR = Total Heat Rejection

(1) All data quoted is gross
(2) Interpolate for water temperatures between those quoted, do not extrapolate
(3) Water flow rate (l/s) = THR/(4.19*ΔT) at 100% Water; for glycol use refer to Ethylene Glycol Correction Factors section

Indoor Air Temperature

+18°C to +28°C

Indoor RH%

+40% to +55%

Condenser Minimum Entering Temperature °C

+25°C

Condenser Maximum Leaving Water Temperature °C

+45°C

Operating Limits