Blue-White FLEX-PRO A2 ProSeries Peristaltic Pump User Manual
Page 17

Page 17
Flex-Pro
Step 8
You can now modify other settings in Mode 0 or you can exit
Setup by; press and hold SELECT RUN MODE button for a
few seconds until you return to Run screen.
Mode 0
set
0
Step 5
Output signal at minimum speed will now be displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release RIGHT arrow.
4
M
A
OUT
4-20 mA Icon
MIN
Step 6
Maximum pump speed will be displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release RIGHT arrow.
Mode 0
100.0
0
M
A
OUT
4-20 mA Icon
SPEED
Step 7
Output signal at maximum speed will now be displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release RIGHT arrow.
20.0
M
A
OUT
4-20 mA Icon
Mode 0
0
Example 1
6
4
8 10 12 14 16 18 20
0
25
50
75
100
Pump Motor Speed (%)
Milliamp Output (mA)
Signal
0% Pump Output = 4 mA
100 % Pump Output = 20 mA
Example 2
6
4
8 10 12 14 16 18 20
0
25
50
75
100
Pump Motor Speed (%)
Milliamp Output (mA)
Signal
0% Pump Output = 4 mA
50% Pump Output = 16 mA
7.3
Mode 0 - Set 4-20mA Output - Continued