Flex-Pro

Step 8

You can now modify other settings in Mode 0 or you can exit
Setup by; press and hold SELECT RUN MODE button for a
few seconds until you return to Run screen.

Mode 0

set

0

Step 5

Output signal at minimum speed will now be displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release RIGHT arrow.

4

M

A

OUT

4-20 mA Icon

MIN

Step 6

Maximum pump speed will be displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release RIGHT arrow.

Mode 0

100.0

0

M

A

OUT

4-20 mA Icon

SPEED

Step 7

Output signal at maximum speed will now be displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release RIGHT arrow.

20.0

M

A

OUT

4-20 mA Icon

Mode 0

0

Example 1

6

4

8 10 12 14 16 18 20

0

25

50

75

100

Pump Motor Speed (%)

Milliamp Output (mA)

Signal

0% Pump Output = 4 mA
100 % Pump Output = 20 mA

Example 2

6

4

8 10 12 14 16 18 20

0

25

50

75

100

Pump Motor Speed (%)

Milliamp Output (mA)

Signal

0% Pump Output = 4 mA
50% Pump Output = 16 mA

7.3

Mode 0 - Set 4-20mA Output - Continued