Blue-White FLEX-PRO A2 ProSeries Peristaltic Pump User Manual

Page 21

Advertising
background image

Page 21

Flex-Pro

Step 7

To exit Setup, press and hold SELECT RUN MODE button
for a few seconds until you return to Run screen.

Step 6

mA value linked to minimum pump speed will now be
displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release RIGHT arrow.

20

M

A

2

Mode 2

Mode 2

OFF

mA

2

Example 1

6

4

8 10 12 14 16 18 20

0

25

50

75

100

Pump

Motor Speed (%)

Milliamp input (mA)

from external source

4 mA = 0% Pump Output

20 mA = 100% Pump Output

Example 2

6

4

8 10 12 14 16 18 20

0

25

50

75

100

4 mA = 100% Pump Output

20 mA = 0% Pump Output

Example 3

6

4

8 10 12 14 16 18 20

0

25

50

75

100

4 mA = 20% Pump Output

16 mA = 43.8% Pump Output

0%

Output

Pump

Motor Speed (%)

Pump

Motor Speed (%)

100%

Output

100%

Output

0%

Output

43.8%

Output

20%

Output

Milliamp input (mA)

from external source

Milliamp input (mA)

from external source

Runtime Screen Shot 1

Mode 2

9.1

Mode 2 - 4-20mA Input Screen Shots

Runtime Screen Shot 2

Mode 2

9.6

mA

2

9.0

Mode 2 - 4-20mA Input

- Continued

Operation

Display motor speed percentage.
Pump Running in 4-20mA Input Operation

Display current 4-20mA input signal
Press and release RIGHT arrow to view mA input value
in real-time.

35.0

SPEED

2

Runtime Screen Shot 3

Mode 2

9.6

mA

2

Press and release RIGHT arrow again to view mA output
value in real-time

(available on select models only)

.

Press and release RIGHT arrow again to view motor
speed percentage
, as in Screen Shot 1.

OUT