Used to remotely control pump with an incoming 4-20 mA signal.
Default setting: 4 mA signal = 0.1% motor speed
20 mA signal = 100.0% motor speed
Time-out - Flex-Pro pumps have a time-out setting of 20 seconds while in configuration menus. If built-in timer exceeds 20 seconds
without a button being pressed, then pump will exit configuration menu. Changes will only be saved after RIGHT arrow button is
pressed and released.
Step 1
Press and release STOP button
Note: Mode cannot be changed while pump is in running.
Press and release SELECT RUN MODE button multiple
times until Mode 2 is selected.
Step 2
With Mode 2 selected, press and hold SELECT RUN MODE
button until ‘Speed’ icon begins flashing.
This indicates that you’ve entered Setup menu.
Step 3
Minimum pump speed will be displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release RIGHT arrow.
Step 5
Maximum pump speed will be displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release RIGHT arrow.
Mode 2
6
4
8 10 12 14 16 18 20
0
25
50
75
100
Pump Motor Speed (%)
Milliamp Output (mA) Signal
Default Setting
2
SPEED
Mode 2
0.1
Mode 2
OFF
mA
MIN
2
SPEED
2
100.0
Step 4
mA value linked to minimum pump speed will be
displayed.
To increase value, press and release UP arrow.
To decrease value, press and release DOWN arrow.
To save value, press and release RIGHT arrow.
2
M
A
Mode 2
4.0
MIN
Mode 2
0.1
MIN
2
SPEED
9.0
Mode 2 - 4-20mA Input Operation