SPECIFICATIONS
Temperature Limits:
-30 to 180°F (-35° to 82°C) standard.
ATEX and IECEx compliant at Ambient Temperature -4 to 146°F (-20 to 63.6°C).
Process Temperature: -4 to 146°F (-20 to 63.6°C).
Maximum Operating Pressure: 1200 psig (82.6 bar).
Maximum Pressure Without Bursting: 3000 psig (210 kg/cm

2

).

Process Connection: 1/4˝ or 1/2˝ female NPT.
Electrical Ratings: SPDT or DPDT contacts rated 15A @ 125/250/480 VAC (V~),
1/8 HP @ 125 VAC (V~), 1/4 HP @ 250 VAC (V~), 1/2A @ 125 VDC (V ) resistive,
1/4A @ 250 VDC (V ) resistive.
Wiring Connections: 3 screw type.
Conduit Connections: 3/4˝ female NPT.
Setpoint Adjustment: 7/16˝ hex nut, field adjustable.
Housing Material: Die cast aluminum.
Finish: Textured gray polyurethane.
Connection Material: Aluminum, brass or 316SS.
Diaphragm: Buna-N or fluorocarbon.
Weight: 3-1/2 lbs. (1.59 kg).
Enclosure Ratings: Weatherproof and Explosion-proof. Listed with UL and CSA for
Class I, Groups B, C and D; Class II Groups E, F and G. UL-NEMA 4X, CSA-NEMA
4. ATEX Compliant 0344 II 2 G Ex d IIC T6 Gb -20 ≤ Tamb ≤63.6°C. Process
Temperature ≤63.6°C. Type Certificate No.:KEMA 04ATEX2186 X. IP56 without
drain and IP 54 with drain. ATEX Standards: EN 60079-0: 2009; EN60079-1: 2007.
IECEx Certified: For Ex d IIC T6 Gb -20 ≤ Tamb ≤63.6°C Process Temperature
≤63.6°C. IECEx Certificate of Conformity: IECEx DEK 11.0095 X; IECEx Standards:
IEC 60079-0: 2007; IEC 60079-1: 2007.

Series SA1100 Pressure Switches actuate one or two single pole, double throw
(SPDT) snap switches in response to increasing or decreasing pressure of
compatible gases or liquids. Three field adjustable operating ranges are available
allowing setpoints up to 500 psig (35 kg/cm

2

). All models are weather-proof and

suitable for hazardous locations as detailed in the chart at lower right. Read and
understand these instructions completely before proceeding with installation or
operation.

Series SA1100 Pressure Switches Weatherproof, Explosion-Proof

Specifications - Installation and Operating Instructions

Bulletin IN-1100

MERCOID DIVISION

Phone: 219/879-8000

www.dwyer-inst.com

DWYER INSTRUMENTS, INC.

Fax: 219/872-9057

e-mail: [email protected]

P.O. BOX 258 • MICHIGAN CITY, INDIANA 46360, U.S.A.

Example

Construction

Adjustable

Pressure

Ranges

Circuit

(Switch)

Options

Pressure
Chamber

Material

Diaphragm

Material

Circuit

(Switch) Type

Process

Connection

Options

SA11

SA11

13

11
12
13

E

E

HS
HG

A

A
B
S

4

4
5

K

K
L

1

1
2

AT
IEC
DR

SA1113E-A4-K1 Pressure Control; weatherproof, NEMA 4X, explosion-proof NEMA 7 & 9; aluminum pressure chamber,
Buna-N diaphragm and O-ring; 1/4˝ female NPT process connection; adjustable deadband, automatic reset; SPDT snap
acting switch; adjustable range 30-500 psig.
Series Designator, weatherproof NEMA 4X, explosion-proof NEMA 7, 9
10 - 150 psig (0.7 - 10 bar)
20 - 250 psig (1.4 - 17.2 bar)
30 - 500 psig (2.0 - 34.0 bar)
Snap action switch rated 15A @ 125/250/480 VAC, 1/8 HP @ 125 VAC,
1/4 HP @ 250 VAC, 1/2 A @ 125 VDC resistive, 1/4 A @ 250 VDC resistive.
Hermetically sealed snap action switch rated 5 A@ 125/250 VAC, 5 A resistive @ 30 VDC*
Hermetically sealed snap action switch with gold contacts rated 1 A @ 125 VAC, 1 A resistive @ 30 VDC*
Aluminum
Brass
316SS
Buna-N diaphragm and O-ring
Fluorocarbon diaphragm and O-ring
SPDT
DPDT (not available with HS or HG switch options)
1/4˝ female NPT
1/2˝ female NPT
ATEX certified construction.
IEC IECEx certified construction
Housing with drain - allows condensate to be drained from inside enclosure (meets NEMA 3R instead of 4X)

MODEL CHART - SERIES SA1100

*Options that do not have ATEX and IECEx.
Attention: Units without the “AT” suffix are not Directive 94/9/EC (ATEX) compliant. These units are not intended for use in potentially hazardous atmospheres in the EU.