Ouellet OTH800D User Manual

Installation instructions, Material, Installation guidelines

Advertising
background image

Installation

Instructions

For models: OTH700S (240GA) /

OTH702S (120GA) / OTH800D (240D)

Material

!

One (1) power base

"

Two (2) screws

#

Four (4) solderless connectors for copper wires

NOTE:

Special CO/ALR solderless connectors must be used when

connecting with aluminum conductors.

$

One (1) floor sensor and one (1) flat tip screwdriver (OTH700
series only)

Installation Guidelines

Turn off power to the heating system at the main power panel
to avoid electrical shock. Installation should be carried out by
an electrician.

High voltage thermostats must be installed onto an electrical
box.
For a new installation, choose a location about 5 ft. above the
floor.
The thermostat must be installed facing the heating system
(except for floor heating installations) and on an inside wall.
Avoid locations where there are air drafts (top of staircase, air
outlet), dead air spots (behind a door), direct sunlight, con-
cealed chimneys or pipes or an air diffuser.

OUELLET CANADA INC. ONE (1) YEAR LIMITED WARRANTY

OUELLET CANADA INC. warrants the component parts of the OTH700/OTH800
series against defects in material and workmanship for a one (1) year period from the
date of purchase, under normal use and service, when proof of purchase of such is
provided to the manufacturer.

The obligation of Ouellet Canada inc., under the terms of this warranty, will be to supply
a new unit and this releases the manufacturer from paying the installation costs or
other secondary charges linked to replacing the unit or the component part(s).

180, 3rd Avenue
P.O. Box 188,
L’ISLET, Quebec, Canada G0R 2C0

If you have any questions concerning the installation of this
power base, call our technical support team at:
Tel.:

Quebec area:

(418) 247-3947

Canada / U.S.:

1-800-463-7043

Fax:

(418) 247-7801

Sales:

[email protected]

Web:

www.ouellet.com

Monday to Friday from 8:00 AM to 5:00 PM EST.

Technical Specifications

Storage

: -4°F to 120°F (-20°C to 50°C)

GFCI

: GA = 5 mA, GB = 30 mA trip level

Econo input

: requires a dry contact

Size (H • W • D)

: 124 x 70 x 23 mm (4.89 x 2.76 x 0.91 in)

Certifications

:

Model

Supply

Max. Load Power Conn.

a

a.

Connection type: 4w = 4 wires, DP = Double Pole, SP = Single Pole

GFCI

OTH702S

(120GA)

120 VAC, 50/60Hz

15 A

1800 W

4w/DP

5 mA

120GB

120 VAC, 50/60Hz

15 A

1800 W

4w/DP

30 mA

120S

120 VAC, 50/60Hz

20 A

2400 W

4w/SP

OTH700S

(240GA)

240 VAC, 50/60Hz
208 VAC, 50/60Hz

15 A

3600 W
3120 W

4w/DP

5 mA

240GB

240 VAC, 50/60Hz
208 VAC, 50/60Hz

15 A

3600 W
3120 W

4w/DP

30 mA

240S

240 VAC, 50/60Hz
208 VAC, 50/60Hz

20 A

4800 W
4160 W

4w/SP

OTH800D

(240D)

240 VAC, 50/60Hz
208 VAC, 50/60Hz

15 A

3600 W
3120 W

4w/DP

277S

277 VAC, 50/60Hz

15 A

4155 W

4w/SP

347S

347 VAC, 50/60Hz

15 A

5200 W

4w/SP

Introduction

This power base is designed to power an OTH700/800 Series
control module.
Refer to the technical specifications for maximum resistive load.

R

C

US

R

C

US

18/

05/

2004

400-609-000-B

Figure 1

Figure 2

Installation Steps

!

Connect the rear power base wires (FIGURE 1) to the power
and to the load using solderless connectors for copper wires.

Connecting the floor sensor (Figure 2)

• Insert the probe into one of the two holes available below

the terminal board and connect the wires to terminals 3 and
4 (no polarity needs to be respected).

• The cable follow the wall down to the floor and must not

cross any heating wires nor be directly on or adjacent to a
heating wire. For maximum performance, the sensor probe
should be centered between the wires in the mat. Run the
sensor in a raceway for easy access to a defective sensor.

Connecting the econo input (Figure 2)

• Insert the cable (use an 18 to 22 gauge flexible wirecable)

into one of the two holes available below the terminal board
and connect terminals 1 and 2 of the base to terminals 1
and 2 of the CT240’s auxiliary output or any of the dry con-
tact outputs of the CT241 (Aube telephone controllers).

"

Push the excess wire (except for the probe/econo) back into
the electrical box to prevent interference with the thermostat.

Warning

: the cable must run on the left side of the cavity

located on top of the terminal board. Secure the power base
to the electrical box using the provided screws.

#

BEFORE mounting the control module onto the base,
configure the switches located on the control module (heating

cycles * and display) and install the control module onto the

base (refer to the control module user guide).

*

this power base must be used only with 15-minute heating cycles.

$

Once the control module is installed onto the power base,
return power to heating system.

Advertising