Post Installation

I n s t a l l a t i o n G u i d e l i n e s

Maintenance

INVERTER FEATURE/TRANSFER SWITCH

START UP
Turn OFF AC main breaker
Turn OFF TruePower Combi remote panel switch
Disconnect shore/station power cable
Turn off all loads associated with the TruePower Combi inverter
Turn ON AC main breaker
Verify proper condition of LED indicators per Table 4 in Features section
Begin applying intended and/or connected loads to the TruePower Combi
by turning on breakers one at a time.

NOTE: Be aware of motor loads with significant start-up amperages such
as refrigerators and other motor circuits, be sure that these have started
and are properly running before applying additional motor loads.

Test any connected GFCI outlets for proper function when connected
to the TruePower Combi unit.

CHARGER FEATURE START UP
Turn on AC main breaker
Verify proper condition of LED indicators per Table 4 in Features section

POST INSTALLATION PRE-START CHECKLIST:

VERIFY:
Proper AC connections
L1, L2, N, G, at the TruePower Combi and main AC Panelboard
Proper DC Connections
Battery +, Battery -, Earth at the TruePower Combi and at the battery
and grounding bus.
TruePower Combi remote panel switch is in the OFF position
Battery Voltage is within operating specifications 10.0 VDC – 15.5 VDC
Battery Type Selector switch has been properly set
Presence of AC Power Shore/station power Connected
Status of fuses/circuit breakers. Fuses in holders, breakers in on position,
main AC breaker OFF.

This unit is solid state and requires no constant adjustment or constant attention,
however, the following items should be checked:

Verify LED Status Panel shows no fault condition and indicates
normal operation.
Condition of fuses/breakers check for as-new condition on fuses
(e.g. no discoloration or corrosion) and that a breaker will manually
trip and reset.
Check for proper ventilation and that no debris has collected on the
fan shroud or items have been improperly stored around the inverter.
Check battery terminal connections (both at battery and TruePower
Combi) for corrosion. Immediately upon signs of corrosion clean
with distilled water and reconnect. Use of tap or bottled drinking
water will damage battery plates due to mineral content.
Per manufacturer’s instructions, check and top off batteries
Check wire condition, overheating due to excessively long or too
small conductors will result in hardening of the insulation or even
burn marks at connections. If any of these signs exist, immediately
remedy the situation by installing the proper conductors.

Maintenance Item

Start Up

Monthly

Troubleshooting

!

The TruePower Combi includes advanced fault indication. The following table outlines
LED and buzzer warning combinations. Some of these faults, if exist, require service
from ProMariner.

The first step to any problem is resetting the TruePower Combi unit by turning off and
then on the switch located on the remote panel.

THERE ARE NO USER SERVICEABLE PARTS INSIDE THE TRUEPOWER COMBI UNIT.
DO NOT ATTEMPT TO DISSASEMBLE THE UNIT. EVIDENCE OF DISSASEMBLY
WILL VOID MANUFACTURERS WARRANTY.