6.3.2

HF33: 3-wire transmitter


Electrical diagram for voltage outputs

The maximum permissible cable length can be
determined under consideration of the voltage
drop caused by the current flowing to the devices
connected to the unit. The voltage drop in the
cable depends both on cable resistance and on
the equivalent resistance of the devices
connected in parallel to the unit. The total
resistance connected to each unit output should
be at least 1000 ohms. Cable resistance should
not be more than 1/1000 of the load resistance.


Minimum load requirements apply to the external device or circuit connected to the HF3 transmitter. These
requirements are defined in the “Operation” chapter

Electrical diagram for current outputs



The maximum permissible cable length,
connecting the unit to other devices, is
determined by the total resistance resulting from
the addition of the cable resistance and that of
the devices connected in series with the unit.
This resistance should not exceed 500 ohms.

Terminal block diagram for type D and W



Terminals

Description

V+

Power supply: 15…40 VDC (+)
or 12…28 VAC (Phase)

GND

Power supply (-) or neutral

OUT1

Relative humidity or dew point (+)
OUT-1

OUT2

Temperature output (+)
OUT-2

GND

Ground (tied with other GND)