Operation

7.1 Minimum load requirements for the HF33 with voltage outputs


The following requirements apply to any external device or circuit connected to the HF33 transmitter with
voltage outputs:



















In the situation where the external device uses an internal pull-up resistor the value of this resistor should
meet the requirements shown below. It is also necessary to add a pull-down resistor RL connected to ground
in order to be able to read 100% of the range of the HF33 voltage output.




















HF33 output signal

Input resistance RL

0…1V

>=1kOhm

0…5V

>=5kOhm

0…10V

>=10kOhm

HF33 signal

VCC

R pull-up

RL

0…1V

3.3V

≥ 250 kOhm

1 kOhm

HF33 signal

VCC

R pull-up

RL

0…1V

5.0V

≥ 400 kOhm

1 kOhm

0…5V

5.0V

≥ 400 kOhm

5 kOhm

HF33 signal

VCC

R pull-up

RL

0…1V

10.0V

≥ 1 MOhm

1 kOhm

0…5V

10.0V

≥ 1 MOhm

5 kOhm

0…10V

10.0V

≥ 1 MOhm

10 kOhm