Factory default settings, E-m-hf3-v1_22, 2 factory default settings – ROTRONIC HF3 User Manual

Page 9

Advertising
background image

E-M-HF3-V1_22

Rotronic AG
Bassersdorf, Switzerland

Document code

Unit

HygroFlex HF3 Transmitters and Thermo-
hygrostats: User Guide

Instruction Manual

Document Type

Page 9 of 27

Document title

© 2009-2011; Rotronic AG E-M-HF3-V1_22

4.2 Factory default settings


Note: Configuration of the HF3 by the user and access to its functions requires a PC with the ROTRONIC
HW4 software (version 2.1.1 or higher) installed. Service cable AC3006 or AC3009 is used to connect the
HF3 service connector to a USB port of the PC (see Maintenance > Service Cable).

Configurable Settings

Applicability

Factory default

Unit system (Metric or English)

HF32, HF33, HF34

As per ordering code

Analog signal type (4…20 mA or other)

HF33

As per ordering code

Psychrometric calculation

HF32, HF33, HF34

As per ordering code

Output 1 parameter, scale and unit

HF32, HF33

As per ordering code (%RH or DP)

Output 2 parameter, scale and unit

HF32, HF33

Temperature, unit as per ordering code

Relay 1 set-point potentiometer adjust. span

HF34

As per order (%RH or DP)

Relay 2 set-point potentiometer adjust. span

HF34

As per order (temperature)

Display resolution (optional)

HF32-S, HF33-S

1 decimal

Display backlight (optional)

HF33-S

Always on

Displayed parameters

HF32, HF33

As per ordering code

Trend indicator (display)

HF32-S, HF33-S

Enabled

Device name

HF32, HF33, HF34

Instrument model


Functions

Applicability

Factory default

Humidity / temperature adjustment

HF32, HF33, HF34

Device write protection

HF32, HF33, HF34

Disabled

Limit humidity output to 100 %RH

HF32, HF33

Enabled

Out-of-limit value digital / display alarm

HF32-S, HF33-S

Disabled

Data recording

HF32, HF33, HF34

Enabled (loop mode

– 10 min. interval)

Automatic humidity sensor test

HF32, HF33, HF34

Disabled

Humidity sensor drift compensation

HF32, HF33, HF34

Disabled

Fail safe mode

HF32, HF33, HF34

Disabled

Simulator mode

HF32, HF33

Disabled


o

For a detailed description of all AirChip 3000 / HF3 main functions see document E-T-AC3000-DF-V1

o

Instructions regarding the configuration of the HF3 and access to its functions are provided in the
following manuals:

E-M-HW4v3-Main
E-M-HW4v3-F2-002
E-M-HW4v3-DR-001
E-M-HW4v3-A2-001
E-M-AC3000-CP
.

o

The factory default setting for dew / frost point calculation is frost point below freezing