15 bank automatic switching function setting, Bank automatic switching function selection, Bank auto-switching operation off – TOHO ELECTRONICS TTM200 User Manual

Page 228: Bank auto-switching operation on

Advertising
background image

48-7009-E

6-80

6.15 BANK AUTOMATIC SWITCHING FUNCTION SETTING

■

Bank Automatic Switching Function Selection

SEt23

ZbNK

Setting Contents

Initial

Value

1

bAF

Bank Automatic Switching Function Selection 3

0

0

Bank Auto-Switching Operation OFF

1

Bank Auto-Switching Operation ON

※

In case the “Bank Auto-Switching Operation

ON” is set;

・

The Bank Switching Setting with the FUNC

Key will be invalid.

・

The Bank Switching Setting by DI will be

invalid.

▲▼

key operation will not be possible either.

※

When SET04 bANKH=0, the setting will be

invalid.

There will be no indication either.

※1

Bank Automatic Switching Function Selection (bAF)

This is to set the Bank Automatic Switching ON/OFF. When ON, the bank will be switched

automatically with the selected input by the Bank Automatic Switching Source Setting (bAS).

Setting Range:When 0: Bank Automatic Switching Operation OFF

When 1: Bank Automatic Switching Operation ON

■

Behavior Diagram when Bank Automatic Switching is ON

BANK1

RMP

10

P1

4.0

・

・

・

I

20

D

5

BANK2

RMP

10

・

・

・

BANK3

RMP

10

・

・

・

BANK4

RMP

10

・

・

・

BANK5

RMP

5

・

・

・

BANK6

RMP

5

・

・

・

BANK7

RMP

10

・

・

・

BANK0

RMP

P1

3.0

MA
X

.16
param

et

er

・

・

・

I

0

D

0

SV

P1

2.0

I

10

D

2

P1

4.0

I

20

D

5

P1

4.0

I

20

D

5

P1

4.0

I

20

D

5

P1

4.0

I

20

D

5

P1

2.0

I

10

D

2

SET20
setting

Refer

BANK0

BANK1

BANK2

BANK3

BANK4

BANK5

BANK6

BANK7

PM1

PM2

PM3

PM4

PM5

PM6

PM7

SLH

SLL

SLL≦

<PM1

SV

value

PM1≦
<PM2

PM2≦
<PM3

PM3≦
<PM4

PM4≦
<PM5

PM5≦
<PM6

PM6≦
<PM7

PM7≦
<SLH

Bank Automatic Switching.

Switch the bank in accordance with

the source(SV)..

MAX. 8BANK

①

②

③

④

⑤

④

①

③

① 10℃

PM*

setting

PM1

PM2

PM3

PM4

PM5

PM6

PM7

SLL

SLH

20℃

0℃

40℃

60℃

90℃

120℃

140℃

160℃

200℃

② 35℃

Bank 0

Bank 1

Bank 2

Bank 3

Bank 4

Bank 5

Bank 6

Bank 7

③ 70℃

④ 100℃

⑤ 150℃

Auto-Switching

sorce

Bank No.

8BANK(All Threshold*Setting <PM1 to PM7)>)

Bank 7

Zone

Threshold

Setting

NOTE: When the Bank Automatic Switching Function is (SET23 bAF = 1), please note the following points in

case the parameters “SV, SLL, SLH” is set at SET 20 (Bank);
・

The value of the “SV, SLL, SLH” set at the Bank will be invalid.

・

The Bank registration of “SV, SLL, SLH” will be erased and will go back to the default value.
If (SET 23 bAF = 0) again, the bank registration of “SV, SLL, SLH” are erased, so there is a need to reset.