Chapter 1: Product Description

December 20, 2004

1-6

LTPH-UM-1261-01

Alarms Wire-Wrap Field

Terminate the alarm leads from the CO alarm system to the HMS-318 List 3 shelf. The Alarms wire-wrap field (TB2,
see

Figure 1-2

) is a 26-pin wire-wrap connector and provides a central connection point to the Normally Closed

(NC), Common (COM), and Normally Open (NO) relay contacts for installing optional alarm input connections (see

Table 1-1 on page 1-4

for Alarm descriptions). When an alarm is not active, there is continuity between the NC and

COM connections; when an alarm is active, there is continuity between the NO and COM connections.

Figure 1-4. Alarms Wire-Wrap Field (TB2)

Alarm Cutoff (ACO)

The Alarm Cutoff (ACO) function silences active audible alarms. Alarm cutoff can be achieved by pressing the ACO
button on the front panel of the Management Unit (for example, HMU-319) or by connecting the ACO pin 22 on the
HMS-318 List 3 shelf Alarms wire-wrap field (see

Figure 1-4

on this page and

Table 1-2

) to ground through an

external NO push button switch. The ACO lead can be daisy-chained to other shelves for multi-shelf applications in
the same equipment rack.

!

IMPORTANT

Before making power connections (CO primary power feeds A and B) to the HMS-318 List 3 shelf,
ensure that the Main CO power breaker is off. Otherwise, severe injury to the installer or damage
to the unit may result.

Note:

The NO and COM alarm relay connections can be daisy-chained between HMS-318 List 3 shelves

for multi-shelf applications in the same equipment rack.

NC

C NO

CR IT

AUD

CR IT

VIS

MAJ

AUD

MAJ

VIS

MIN

AUD

MIN

VIS

SYS

ID

ACO

1

2

3

4

5

6

7

8

9

10 11

12

13

14

15

16

17 18

19 20

21

22

0

6

-1

2

6

1

R

1

ALARMS

23 24

GND

E XT

TEMP

25

26

NO COM
FAN

Advertising
This manual is related to the following products: