24 Room Air Conditioner

Maintenance and Service

COMPLAINT

CAUSE

REMEDY

n Grommets
n Fan

n Loose set screw
n Worn bearings

n Voltage

n Wiring

n Rotary

n Thermostat

n Capacitor (Discharge

capacitor before servicing)

n Compressor

n Overload

n Pressure Switch

• Check grommets; if worn or missing, replace them.

• If cracked, out of balance, or partially missing,

replace it.

• Tighten it.

• If knocking sounds continue when running or loose,

replace the motor. If the motor hums or noise appears
to be internal while running, replace motor.

• Check voltage. See the voltage limits. If not within

limits, call an electrician.

• Check the wire connections, if loose, repair or

replace the terminal. If wires are off, refer to wiring
diagram for identification, and replace. Check wire
locations. If not per wiring diagram, correct.

• Check for continuity, refer to the wiring diagram for

terminal identification. Replace the switch if circuit is
open.

• Check the position of knob If not at the coldest

setting, advance the knob to this setting and restart
unit.
Check continuity of the thermostat. Replace
thermostat if circuit is open.

• Check the capacitor.

Replace if not within ±10% of manufacturer's rating.
Replace if shorted, open, or damaged.

• Check the compressor for open circuit or ground. If

open or grounded, replace the compressor.

• Check the compressor overload, if externally

mounted. Replace if open. (If the compressor
temperature is high, remove the overload, cool it,
and retest.)

• Check continuity of the pressure switch. Replace the

pressure switch if circuit is open.

Fan motor noise.

Compressor will
not run, but fan
motor runs.