English, Room air conditioner voltage limits – LG LP090CED User Manual

Page 25

Advertising
background image

Ownerʼs Manual 25

ENGLISH

Maintenance and Service

NAME PLATE RATING

MINIMUM

MAXIMUM

208/230 V

187 V

253 V

265 V

239 V

292 V

ROOM AIR CONDITIONER VOLTAGE LIMITS

COMPLAINT

CAUSE

REMEDY

n Voltage

n Overload

n Fan motor

n Condenser air flow

restriction

n Condenser fins

(damaged)

n Capacitor
n Wiring
n Refrigerating system

n Air filter
n Exhaust damper door
n Unit undersized

n Block at indoor (curtain or

bedclothes etc.) or
outdoor discharge air.

n Cross flow fan

n Copper tubing

• Check the voltage. See the limits on the preceding

page. If not within limits, call an electrician.

• Check overload, if externally mounted.

Replace if open. (If the compressor temperature is
high, remove the overload, cool, and retest.)

• If not running, determine the cause. Replace if

required.

• Remove the cabinet. inspect the interior surface of

the condenser; if restricted, clean carefully with a
vacuum cleaner (do not damage fins) or brush. Clean
the interior base before reassembling.

• If condenser fins are closed over a large area on the

coil surface, head pressures will increase, causing the
compressor to cycle. Straighten the fins or replace the
coil.

• Test capacitor.

• Check the terminals. If loose, repair or replace.

• Check the system for a restriction.

• If restricted, clean or replace.

• Close if open.

• Determine if the unit is properly sized for the area to

be cooled.

• Remove it and make certain there is nothing within

20” back and front of sleeve & front grille.

• Check the set screw or clamp. If loose or missing,

correct. If the blower or fan is hitting air guide,
rearrange the air handling parts.

• Carefully rearrange tubing not to contact, compressor,

shroud, and barrier.

Compressor

cycles on

overload.

Insufficient

cooling or heating.

Excessive noise.