8

N

OTE

: S

ETTINGS ARE ADJUSTED THROUGH

P

OWER

C

HUTE SOFTWARE

OR OPTIONAL

S

MART

S

LOT ACCESSORY CARDS

.

F

UNCTION

F

ACTORY

D

EFAULT

U

SER

S

ELECTABLE

C

HOICES

D

ESCRIPTION

Low Battery Warn-
ing

2 minutes

PowerChute soft-
ware provides
automatic, unat-
tended shutdown
when approxi-
mately 2 minutes
of battery oper-
ated runtime re-
mains.

: Brightly illu-

minated - low bat-
tery warning level of
about 2 minutes.

: Dimly illumi-

nated - low battery
warning level of
about 5 minutes.

: No illumina-

tion; low battery
warning level is
approximately 8
minutes
.

The UPS will beep when 2 minutes of
battery runtime remains.

Change the warning interval setting by
pressing the voltage sensitivity button,

while pressing and holding the

button.

Change the low battery warning inter-
val setting to the time that the operat-
ing system or system software requires
to safely shut down.

Synchronized
Turn-on Delay

0 seconds

0, 60, 120, 180, 240,
300, 360, 420 sec-
onds

Specify the time the UPS will wait
after the return of utility power before
turn-on, (to avoid branch circuit over-
load).

High Transfer
Point

100 V model:
108 Vac
120 V model:
127 Vac
208 V model:
225 Vac
230 V model:
253 Vac

100 V model:
108, 110, 112,
114 Vac
120 V model:
127, 130, 133,
136 Vac
208 V model:
225, 229, 233,
237 Vac
230 V model:
253, 257, 261,
265 Vac

Set the high transfer point higher to
avoid unnecessary battery usage when
the utility voltage is usually high and
the connected equipment is specified
to operate with input voltages this
high.

Low Transfer Point 100 V model:

92 Vac
120 V model:

106 Vac
208 V model:
182 Vac
230 V model:

208 Vac

100V model:
92, 90, 88, 86 Vac
120 V model:

97, 100, 103,
106 Vac
208 V model:
170, 174, 178,
182 Vac
230 V model:
196, 200, 204,
208 Vac

Set the low transfer point lower when
the utility voltage is usually low and
the connected equipment is specified
to operate with input voltages this low.

Output Voltage
230 V Model Only

230 Vac

220, 230, 240 Vac

Select the output voltage.