American Power Conversion 2200 VA User Manual

Page 9

Advertising
background image

7

3: U

SER

C

ONFIGURABLE

I

TEMS

N

OTE

: S

ETTINGS ARE ADJUSTED THROUGH

P

OWER

C

HUTE SOFTWARE

OR OPTIONAL

S

MART

S

LOT ACCESSORY CARDS

.

F

UNCTION

F

ACTORY

D

EFAULT

U

SER

S

ELECTABLE

C

HOICES

D

ESCRIPTION

Automatic Self-
Test

Every 14 days
(336 hours)

Every 7 days
(168 hours),
On Startup Only,
No Self-Test

Set the interval at which the UPS will
execute a self-test.

UPS ID

UPS_IDEN

Up to eight charac-
ters (alphanumeric)

Uniquely identify the UPS, (i.e. server
name or location) for network man-
agement purposes.

Date of Last Bat-
tery Replacement

Manufacture Date

mm/dd/yy

Reset this date when you replace the
battery module.

Minimum Capacity
Before Return from
Shutdown

0 percent

0, 15, 30, 45, 50, 60,
75, 90 percent

Following a low-battery shutdown, the
battery modules will be charged to the
specified percentage before powering
connected equipment.

Voltage Sensitivity

The UPS detects
and reacts to line
voltage distortions
by transferring to
battery operation to
protect connected
equipment.

High

: Brightly illu-

minated - high sensi-
tivity.

: Dimly illumi-

nated - medium sen-
sitivity.

: No illumina-

tion; low sensitivity.

Adjust by pressing the voltage sensi-
tivity
button

(rear panel). Use a

pointed object, (such as a pen) to do
so.

Note: In situations of poor power qual-
ity, the UPS may frequently transfer to
battery operation. If the connected
equipment can operate normally under
such conditions, reduce the sensitivity
setting to conserve battery capacity
and service life.

Alarm Delay Con-
trol

Enable

Enable, Mute, Dis-
able

Mute ongoing alarms or disable all
alarms permanently.

Shutdown Delay

90 seconds

0, 90, 180, 270, 360,
450, 540, 630 sec-
onds

Set the interval between the time when
the UPS receives a shutdown com-
mand and the actual shutdown.