Troubleshooting 32

UPS problems

UPS is not working properly

Action:

1.

Be sure the UPS batteries are charged to the proper level for operation. See the UPS documentation
for details.

2.

Be sure the UPS power switch is in the On position. See the UPS documentation for the location of
the switch.

3.

Be sure the UPS software is updated to the latest version. Use the Power Management software
located on the Power Management CD.

4.

Be sure the power cord is the correct type for the UPS and the country in which the server is located.
See the UPS reference guide for specifications.

5.

Be sure the line cord is connected.

6.

Be sure each circuit breaker is in the On position, or replace the fuse if needed. If this occurs
repeatedly, contact an authorized service provider.

7.

Check the UPS LEDs to be sure a battery or site wiring problem has not occurred. See the UPS
documentation.

8.

If the UPS sleep mode is initiated, disable sleep mode for proper operation. The UPS sleep mode
can be turned off through the configuration mode on the front panel.

9.

Change the battery to be sure damage was not caused by excessive heat, particularly if a recent air

conditioning outage has occurred.

NOTE:

The optimal operating temperature for UPS batteries is 25°C (77°F). For approximately

every 8°C to 10°C (16°F to 18°F) average increase in ambient temperature above the optimal

temperature, battery life is reduced by 50 percent.

Low battery warning is displayed

Action:

1.

Plug the UPS into an AC grounded outlet for at least 24 hours to charge the batteries, and then test
the batteries. Replace the batteries if necessary.

2.

Be sure the alarm is set appropriately by changing the amount of time given before a low battery
warning. Refer to the UPS documentation for instructions.

One or more LEDs on the UPS is red

Action: Refer to the UPS documentation for instructions regarding the specific LED to determine the cause

of the error.

Unknown problem

Action:

1.

Disconnect power to the server.

2.

Following the guidelines and cautionary information in the server documentation, strip the server to
its most basic configuration by removing every card or device that is not necessary to start the

server. Keep the monitor connected to view the server startup process.