Smart-UPS 750/1000/1500/2200/3000 VA 120/230 Vac Tower

Main Outlet Group and the Switched Outlet Group

Overview

The Main Outlet Group and the Switched Outlet Group can be configured to independently turn off, turn
on, shut down, and reboot connected equipment. (These features are not available on the 750 VA units.)

The Main Outlet Group and the Switched Outlet Group can be commanded to do the following:

• Turn off: Disconnect from power immediately and restart only with a manual command

• Turn on: Connect to power immediately

• Shutdown: Disconnect power in sequence, and automatically reapply power in sequence when

utility power becomes available

• Reboot: Shut down and restart

In addition, the Main Outlet Group and the Switched Outlet Group can be configured to do the
following:

• Turn on or off in a specified sequence

• Automatically turn off or shut down when various conditions occur

Note: If the Main Outlet Group and the Switched Outlet Group are not configured, all of the
outlets on the unit will still provide battery back-up power.

Using the Main Outlet Group and the Switched Outlet Group

The Main Outlet Group functions as a master switch. It will turn on first when power is
applied, and shut off last when there is a power outage and battery run-time has been
exhausted.

The Main Outlet Group must be turned on for the Switched Outlet Group to turn on.

1. Connect critical equipment to the Main Outlet Group.

2. Connect peripheral equipment to the Switched Outlet Group.

– Nonessential equipment that should shut off quickly in the event of a power outage to conserve

battery runtime can be added to a short power-off delay

– If equipment has dependent peripherals that must restart or shut down in a specific order, such

as an ethernet switch that must restart before a connected server, connect the devices to
separate groups

– Equipment that needs to reboot independently from other equipment should be added to a

separate group

3. Use the Configuration menus to configure how the Switched Outlet Group will react in the event

of a power outage.

Customize the Main Outlet Group and the Switched Outlet Group

Use the Control menus to change the Switched Outlet Group and the Main Outlet Group settings.