Erm rear panel – HP UPS Extended Runtime Module User Manual

Page 12

Advertising
background image

Component identification 12

NOTE:

If the UPS was operating on battery power when the remote switch was closed, no

power is available to the load devices until utility power is restored and the UPS has been
manually powered up.

To restore power to the load devices after the REPO feature is activated, press the On button after the AC
source is reconnected to the UPS.

IMPORTANT:

Pressing and holding the On button without utility present normally initiates a

battery start and the UPS assumes the load. However, if the On button is pressed and a REPO
is detected, battery start is inhibited and the UPS is not able to assume the load. The
electronics module fan spins and the General Alarm LED and an audible alarm are active as
long as the On button is held.

To power down the entire network in the event of an emergency, the REPO ports of multiple UPS units can
be connected to a single switch.

ERM rear panel

Item

Description

1

ERM input connector (from another ERM output)

2

Circuit breaker

3

ERM output connector (to the UPS or another ERM)