HP ProLiant DL360 G5 Server User Manual

Page 59

Advertising
background image

Hardware options installation 59

16.

Connect and route the battery pack power cable to the HP Smart Array P400i Controller cache
module.

17.

Install fan modules 1 and 2 ("

Remove and install a fan module

" on page

22

).

18.

Install the air baffle.

19.

Install the access panel (on page

20

).

20.

Slide the server into the rack.

21.

Power up the server (on page

18

).

Upgrading the HP Smart Array P400i Controller to support six hard drives

In certain configurations, the server may ship configured with the HP Smart Array P400i Controller and
only one data cable installed. To enable support for six hard drives, install an optional Mini-SAS 4i
0.35 m (14 in) cable from the HP Smart Array P400i Controller to the hard drive backplane.

1.

Power down the server (on page

18

).

2.

Extend the server from the rack (on page

19

).

3.

Remove the access panel (on page

20

).

4.

Remove the air baffle. ("

Remove the power supply air baffle

" on page

21

, "

Remove the processor

air baffle

" on page

22

)

5.

Remove fan modules 1 and 2 ("

Remove and install a fan module

" on page

22

).

6.

Connect and route the second cable.

CAUTION: When routing cables, use the cable trough between fan modules 1 and 2. Be sure the cables

do not interfere with fan module installation. Be sure to route the cables around the access panel mounting
pin bracket so as not to interfere with access panel installation.

Advertising