Outback Power Systems VFX Series Programming Manual User Manual

Page 7

Advertising
background image

6

Use the search sensitivity screen to determine

the size of an AC load needed for the FX to turn

ON and leave SEARCH mode.

• Pressing decreases sensitivity (a

bigger load is needed to turn the FX on)

• Pressing increases the sensitivity

which means a smaller load (less wattage) will

turn the FX on

• Decreasing to zero disables SEARCH mode

Press to view the next SEARCH screen.

The FX produces pulses to detect AC loads. The

search pulse length screen allows adjusting the

number of pulses (from 4 to 20) or cycles to

more reliably detect AC loads. A setting of 8 or

higher, adjusted using and ,

is recommended. Press to open the

search pulse spacing screen.

The search pulse spacing screen adjusts the

amount of time the FX waits before producing

additional AC pulses to sense a load. The higher

the number of cycles, the lower the FX power

consumption, but the longer it takes before the

AC load is powered. The cycles range from 4 to

120 cycles (two seconds). Press to

complete the SEARCH menu.

SETUP/FX/SEARCH--------P00
search

6

sensitivity

DOWN INC DEC PORT

SETUP/FX/SEARCH--------P00
search

8 cycles

pulse length

DOWN INC DEC PORT

SEARCH MODE

An FX consumes a small amount of power when it is not actively supplying power to loads or for

battery recharging. During this SEARCH MODE, the FX sends out AC pulses to sense load demands.

Once a large enough load is sensed, the FX turns ON and provides AC power. Using SEARCH mode, a

user can adjust the FX so it only comes ON for certain size loads and not for smaller ones. The SEARCH

features are mainly used in off -grid systems to conserve power.

NOTE: Some loads will require experimenting with the SEARCH settings.

SETUP/FX/SEARCH--------P00
search

60 cycles

pulse spacing

DOWN INC DEC PORT

INC

DEC

DOWN

DEC

INC

DOWN

DOWN

Advertising