Gmm20w co, Module, Technical data – Vaisala GMM20W User Manual
Page 4

GMM20W CO
2
module
Sensor Systems Division
U300en-1.1
1999-11-16
TECHNICAL DATA
Carbon dioxide
Measuring range
0...2000 ppm CO
2
(nominal)
(can be recalibrated for other ranges: 0...5000 ppm, 0...10000 ppm, 0...20000 ppm)
Accuracy at 20°C
<
±[
1% FS + 1.5% of the reading
]
(including non-linearity and calibration uncertainty)
Repeatability
<+1 % FS
Temperature dependence
of output
< 0.05 %FS / °C
Long-term stability
(in ambient conditions)
<
±
5 % / 5 years
Response time (0...67%)
1 minute
Operating conditions
Operating temperature
-5...+45 °C
Storage temperature
-20...+70 °C
Humidity range:
temporarily
0...100 %RH (non-condensing)
continuous use
0...85 %RH (non-condensing)
General
Output signals
0...20 mA or 4...20 mA and 0...10 V
Optional outputs
relay
LonWorks
interface
Recommended external
load: current output
max. 500
Ω
voltage output
min. 1k
Ω
Relay contact ratings
max. 50 V 0.5A
Power supply
nominal 24 VDC/VAC (18...30 VDC)
Power consumption
< 2.5 W
Warm-up time
< 5 minutes
Dimensions:
72 x 74 x 19 mm
Weight:
56 g
Accessories
Order code
Description
GMI21
Display and relay option
GMR20
Relay output option
GML20
LonWorks
interface option
19222GM
Calibration software kit (incl. disk and serial COM adapter)
18192GM
Field calibration kit (used with Vaisala’s portable CO
2
meters)
The GMM20W module complies with the following standards and has passed the following
tests:
EN50081-1 (EN 55022 class B)
EN50082-1 (IEC 1000-4-3, IEC 801-4 (1988) )