ON/OFF CONTROL
ON/OFF and PID control can be used for the heat and cool output in several
combinations. The following lists the valid control modes:
OP1 & OP2 VALID CONTROL MODES
OP1 MODE OP2 MODE MANUAL MODE OUTPUT
POWER RANGE
OP1 STATE
OP2 STATE
PID
0% to +100.0%
OP1-TP
ON/OFF
(PrOP=0.0)
+100.0%
OP1-ON
Any other setting
OP1-OFF
PID
PID
-100.0% to +100.0%
OP1-TP
OP2-TP
PID
(GAN2=0.0)
ON/OFF
0% to +100.0%
OP1-TP
OP2-OFF
-100.0% to 0%
OP1-TP
OP2-ON
ON/OFF
(PrOP=0.0)
ON/OFF
(GAN2=0.0)
+100.0%
OP1-ON
OP2-OFF
-100.0%
OP1-OFF
OP2-ON
Any other settings
OP1-OFF
OP2-OFF
TP - Time Proportioning
Note: In manual mode, the % output power is not limited to the output power limits
(OPLO & OPHI).
-68-