5.5.2 Terminal assignments

Power input

N

Terminal - power input

Neutral conductor

L

Terminal - power input

Phase

Actuating signal output

Y

i

Terminal - output signal

+...20 mA DC

Y

u

Terminal - output signal

+...10 V DC

Terminal - ground, GND.................0 V

Potentiometer input

R

P

Potentiometer ...............................0...1000



R

a

Terminal - potentiometer input

dashed line (yellow wire)

must‘nt be connected because R

a

is internally wired with

R

b

R

b

Terminal - potentiometer input ......(grey wire)

R

c

Terminal - potentiometer input

(red wire)

Fig. 5

5.5.3 Connection Conditions
All electrical terminals are connected to the electronic position
indicator RI21 by means of series isolating terminals. The
suitable conductor cross-sections for connecting the terminals
are 0.2 to 2.5 mm

2

. To achieve optimal electromagnetic

compatibility it is recommended to use shielded cables for
connecting potentiometers or standardized active current or
voltage signals.
Please contact the manufacturer direct for technical
information.

ATTENTION !
To facilitate use in 3-conductor technology, the ground output

 may be

connected to the N contact of the power input only in the 24 V AC version.

The new contact is then referred to as zero potential (0V)

Fuse protection of mains power supply on system side: 6 A max.

5.6 Connection in Control Cabinet

Power input for connection in control cabinet
The voltage supply is connected to terminals N and L in accordance with the type
identification plate.
Actuating signal output for connection in control cabinet
The actuating signal output ...20 mA is connected to terminals Y

i

and

.

The actuating signal output ...10 V is connected to terminals Y

u

and

.

ATTENTION !
Only one actuating signal output may be connected at any one time.

Potentiometer input for connection in control cabinet
A 1000 Ohm potentiometer is connected to terminals R

a

, R

b

, R

c

.

The wiper is connected to R

b

.

With the valve closed, there are 0 Ohms between R

b

and R

c

.

............

...................

............

...................

............

.................

...........

.................

............

..........

...........

...............

..........

...........

.......

Advertising