Hydraulic fan system controller – hfs-3-12v, Non-inverted valve control operation – High Country Tek HFS-3 User Manual

Page 10

Advertising
background image

Hydraulic Fan System Controller – HFS-3-12v

10

• Plug driver unit onto valve coil to be driven.
• Remove ‘HFS-3’-12v securing screw
• Remove ‘HFS-3-12v’ opaque lid to reveal internal adjustments.
• Ensure command PWM signal is set to zero.
• Ensure that all wire connections are correct and secure.
• Turn I Min potentiometer 1 turn Anti-Clockwise ( Minimum ).
• Turn I Max potentiometer 20 turns Clockwise ( Maximum ).
• Apply 12VDC ( +10 to +14VDC absolute Maximum ) to the driver plug.

NON-INVERTED operation

means that the output current follows the input command signal.

i.e. 10% PWM = Min O/P

90% PWM = Max O/P

This option is intended for use with a proportional flow control or variable pump electro-hydraulic stroker.

In this configuration, if the power supply fails, the fan unit will default to the OFF speed.

For this option to be activated, the user must

remove

( by cutting )

link ‘A’, the location of which

is shown at the bottom of this page.

CAUTION:-

Link ‘A’, once removed, CANNOT be replaced.

• Slowly increase command to approx 90% of maximum PWM.
• Use the I Min adjustment to give minimum motor speed required.
• Slowly Increase command signal to 10% of maximum setting.
• Adjust I Max until desired motor maximum speed is achieved.

• Check that ‘Output ON’ led is functioning proportionally by varying the command signal.

Ensure

link ‘A’, is cut and REMOVED

Adjustment Guide:

NON-INVERTED valve control operation.

Link ‘A”