Top down™ td-series piping installation, Domestic water piping, Boiler piping – Amtrol BoilerMate Top Down User Manual

Page 6

Advertising
background image

-6-

5. TOP DOWN™ TD-SERIES

PIPING INSTALLATION

DOMESTIC WATER PIPING

1. Connect the cold water supply to the pipe labeled COLD

WATER

2. Connect the HOT WATER piping to the domestic hot water

system.

3. Make an 8-inch “heat trap” on the HOT WATER outlet as

shown in the diagram. This will reduce standby losses from

heat migrating up the piping.

4. When all domestic water piping is complete, open the cold

water supply and allow some water to enter the tank. Look

and listen for signs of leaks and repair as necessary before

continuing.

Note: If installing on a city supply, ensure a dedicated

Thermal Expansion tank (Therm-X-Trol

®

or equivalent) is

used.

5. Install a blowdown tube on the T&P relief valve outlet.

Plumb to within 6 inches above a floor drain or as directed

by plumbing code.

BOILER PIPING

1. Plumb the circulator or zone valve on the BOILER SUPPLY

line. If using a separate circulator, the pump flange

can be mounted directly to the threaded pipe marked

BOILER SUPPLY. Alternately, the circulator can be placed

anywhere on the boiler supply line.

2. Pipe the BOILER RETURN connection to the boiler return

line.

Be sure the return line is NOT

plumbed to the suction side of any

heating circulators. This may require moving the

heating circulator off the boiler tapping on packaged

boilers. Failure to do so will result in overheating and

tank damage when the heating system is in

operation.

3. Install a weighted flow check on the boiler return line. This

is not necessary on systems utilizing a zone valve to control

the BoilerMate

®

temperature.

4. After completing the boiler piping, slowly open the boiler fill

valve and pressurize the BoilerMate

®

loop. Check for leaks

and repair as necessary. Proceed to the appropriate wiring

section in this manual.

If installing on city water supply a

properly sized THERM-X-TROL

®

is

required with the BoilerMate

®

and should be installed as set

forth in the THERM-X-TROL

®

product installation manual.

LEFT SIDE . . . . . . . . . . . . 1”

RIGHT SIDE . . . . . . . . . . . 1”

TOP . . . . . . . . . . . . . . . . . 9”

REAR . . . . . . . . . . . . . . . . 1”

FLOOR . . . . . . . . . . . . . . . 0”

FRONT . . . . . . . . . . . . . . . 1”

Clearance From Combustible Surfaces

LEFT . . . . . . . . . . . . . . . . . 12”

RIGHT. . . . . . . . . . . . . . . . 12”

FRONT . . . . . . . . . . . . . . . 30”

HEAD ROOM . . . . . . . . . . 9”

REAR . . . . . . . . . . . . . . . . 1”

Recommended Clearance For Servicing

T&P RELIEF VALVE OUTLET

HOT WATER OUTLET

BOILER RETURN
(Bottom Left)

BOILER SUPPLY
(Bottom Right)

COLD WATER INLET
(Top Center)

DRAIN VALVE