Installation Guide APC BC300 Series 40kW 208/450/480V UPS

990-1401

Installation

3.0 Installation

3.1

Requirements on Site

A 3-foot free space on all sides should be allowed during installation. Place the UPS in a clean,
dust-free environment, free of contaminants. Allow air circulation around the UPS cabinet and
any battery cabinets or racks.

•

Ambient temperature range: 32 to 104° F (0 to 40° C).
Ideal temperature: 77° F (25° C)

NOTE:

At 92° F (33° C), battery life would be approx. 50% compared to storage at a

normal temperature of 77° F (25° C). At 113° F (45° C). Battery life will be reduced
to some 25%. Make sure that the floor can support the weight of the UPS, external
batteries, and any other necessary equipment.

•

Never install systems in direct sunlight or near heat sources.

•

Service access from front and top of unit. Cable entry from bottom of unit.

•

Do not operate the UPS or batteries in a sealed room or container.

NOTICE!

Allow a minimum clearance of 3 foot (914mm) for service in front of and above the UPS and 6
inches (152mm) at the back.

NOTICE!

Do not stand on the UPS. Keep the UPS cabinet surface free of objects.