990-1401

Installation Guide APC BC300 Series 40kW 208/450/480V UPS

7

3.1.1 UPS Footprint (measurements in inches & mm)

Figure 1 - Footprint

3.2

Installing the Conduit Connection Kit

Insulated and other tools required

•

13 mm ratchet or wrench

•

T20 torx screwdriver

•

Greenly punch

•

Equipment suitable for lifting heavy UPS off the ground

36.00 (914)

Minimum Service

Clearance

39.4

(1000)

31.7

(804)

59.1

(1500)

A

A

Front View

Side View

36.00 (914)

Recommended

Cooling

Clearance

31.7

(804)

Section A-A

View From Inside Cabinet, Looking Down

Conduit

Connection

Box

Cable Entry

(Rear)

(Front)

17.9

(455)

17.9

(455)

39.4

(1000)

19.8

(504)

27.9

(708)

31.7

(804)

Notes:
1. All dimensions are in inches (millimeters).
2. Minimum cooling and service clearance 36.00 (914).
3. Conduit entry is bottom of unit.
4. Unit weight = 1798lbs (815kg)
5. Installation must comply with all applicable national and local codes