8.

To determine the firing rate for NATURAL gas, accurately time test dial for the number
of seconds for one revolution and use the following formula. All other gas utilization
equipment must be off.

3600 x test dial size x BTU value

= BTU/Hr.

No. of seconds for one rev. test dial

Then divide by 1,000 for MBH value.

Example:

3600 x 1 x 1000

= 360,000 BTU/HR = 360 MBH

10

10

Part 1

Installation

Continued

Part 1 Installation

RE6700B

2.4

2.1

2.2

2.4

2.3

2.5

2.2

2.5

2.4

2.0

0.563

0.563

0.484

0.422

0.404

0.358

0.332

0.297

0.277

0.277

2.5

2.3

2.7

2.3

2.8

2.3

2.1

3.0

2.2

2.2

No Orifice

No Orifice

0.563"

0.563"

0.484"

0.484"

0.422"

0.358"

0.358"

0.332"

700

650

600

550 *

500

450

400

350

300

275

Table 3: Capacity and Preliminary Gas Settings

1. Adjust the main regulator to vary the manifold gas pressure and burner input within the range shown.

Do not exceed pressure as listed in Table 3, under any circumstances. Use combustion readings (CO
or O2) to determine exact inputs.

2. If you need an orifice that is not included with the burner, drill out the provided 0.358 orifice

(stamped J ) to the required hole size as per chart above

3. Natural gas to LP gas conversion kits are available, consult factory.

*

Orifice size and approximate manifold gas pressure setting as shipped. Air shutter is set on mark 4.

DATA FOR TABLES IS APPROXIMATE AND BASED ON “0" OVERFIRE PRESSURE AT SEA LEVEL

2.5

2.3

2.7

2.4

2.1

2.2

2.4

2.3

2.5

2.2

2.5

2.4

2.0

No Orifice

No Orifice

0.563"

0.563"

0.563"

0.484"

0.422"

0.404"

0.358"

0.332"

0.297"

0.277"

0.277"

3.7

3.5

2.9

2.5

2.3

2.7

2.3

2.8

2.3

2.1

3.0

2.2

2.2

No Orifice

No Orifice

No Orifice

No Orifice

No Orifice

0.563"

0.563"

0.484"

0.484"

0.422"

0.358"

0.358"

0.332"

Input

MBTU/HR

1

Orifice

Size

(Inches)

Natural Gas

Natural Gas / Propane Gas Orifice Size and Pressure Settings

Manifold

Pressure

("W.C)

Orifice

Size

(Inches)

825

800

750

700

650

600

550 *

500

450

400

350

300

275

Propane Gas

Manifold

Pressure

("W.C)

-

-

-

-

-

H

H

O

O

F

J

J

K

-

-

H

H

H

O

F

P

J

K

L

N

N

Letter

Stamp

Letter

Stamp

-

-

H

H

O

O

F

J

J

K

H

H

O

F

P

J

K

L

N

N

Note: Manifold Pressure settings are based on zero back pressure

RE6850 & RE6850B

VIII

Initial Start-

up /Adjustment

Continued