Part 1 installation – Midco Economite RE6850B User Manual

Page 6

Advertising
background image

6

____________________________________________

CAUTION: The available gas pressure should be within the limits shown in

SPECIFICATIONS section. Excessive pressure may damage electric valves, regulators
and manual valves. If the supply pressure exceeds the 14.0"W.C. maximum, a suitable
high pressure regulator must be installed between the Main Manual Shut-Off Valve and
burner shut-off valve as shown in Figure 5.

Part 1

Installation

Continued

Part 1 Installation

VI

Piping

Capacities shown are for a
total pressure drop of
0.3"W.C. For 0.5"W.C.
pressure drop, multiply
capacity shown by 1.3 .
Propane capacities shown
are for a total pressure drop
of 0.5” W.C. For higher
permissible pressure drops,
consult your gas supplier.

Table 2: Schedule 40 NPT

Pipe-Capacity Chart

10

200

590

400

1075

900

40

275

200

500

450

1040

650

75

190

150

360

325

750

475

20

150

400

275

730

600

900

Pipe
Size

3/4

3/4

1

1

1 1/4

1 1/4

1 1/2

1 1/2

Natural

Propane

Natural

Propane

Natural

Propane

Natural

Propane

100

160

300

275

630

400

975

Approximate Capacity -MBH

Pipe Length

Type

of Gas

V

Electrical

Continued

Wiring Diagram for RE6850 - 120V